Lounge power points dead
- Customer report
- The two power points by the lounge window stopped working. The one by the door still works. Kitchen and bedrooms are fine. Nothing has tripped.
- Circuit
- Radial 20 A power circuit from an RCBO in the switchboard. GPO 1 (by the door) loops on to GPO 2, then GPO 3 (by the window). Nothing is plugged in at GPO 2 or 3.
- Your job
- Find the fault with the fewest tests, working safely. The fault is different each time. Every test costs 2 points, unsafe steps cost more.
Circuit
Safety actions
Live tests are done energised with insulated probes and the right PPE. Dead tests need the circuit isolated, locked, tagged and proved dead.
Choose a test
Score
100Call the fault
Reviewer table
Pick a fault to see every reading the simulator shows for it. Chapter reference: [Jordan to add Bible chapter]
| Test | Condition | Reading | What it tells you |
|---|